Pinnacle Pipeline Company
ORIGINAL VOLUME NO. 1
Contents / Previous / Next / Main Tariff Index
Effective Date: 10/08/2003, Docket: RP04-102-001, Status: Effective
Original Sheet No. 112 Original Sheet No. 112 : Effective
designated by the specifications referenced in
Section 2.1, as determined in accordance with
Section 3.7, the gross calorific heating value
will be adjusted to reflect the actual water
vapor content of the gas accordingly for billing
purposes.
In the event gas is received into Transporter's
pipeline system from an interconnect other than
the Receipt Point defined herein, Shipper may
request and, upon such request, Transporter shall
be required to install an automatic sampling
device to measure the hydrogen sulfide levels in
the gas. The hydrogen sulfide content of the gas
shall be determined in accordance with the Gas
Processors Association Standard for such
determination then in effect, and if there is no
such standard in effect, by a method generally
used and accepted in the industry and agreeable
to both Transporter and Shipper.
3.9 Determination of Total Delivered MMBtu - The
total number of MMBtus delivered shall be
determined by multiplying the delivered gross
calorific heating value, as determined in Section
3.8, by the total volume of gas as determined in
Section 3.1. If the total MMBtu results obtained
by use of Transporter's equipment, as specified
in Section 3.1 and 3.8, differ by one percent or
more from the results obtained by use of
Shipper's check metering equipment, then
Transporter and Shipper shall each be required to
calibrate its measurement equipment. If such
calibrations indicate that Transporter's
measurement equipment is within the tolerance
levels set forth in Section 3.5, then
Transporter's measurement equipment shall
continue to be used. If such calibrations
indicate that Transporter's measurement equipment
is not within the tolerance levels set forth in
Section 3.5 and that Shipper's measurement
equipment is within the tolerance levels set
forth in Section 3.5, then Shipper's measurement
equipment shall be used. If such calibrations
indicate that neither parties' measurement
equipment is within the tolerance levels set
forth in Section 3.5, then the provisions of