Riverside Pipeline Company, L. P.
First Revised Volume No. 1
Contents / Previous / Next / Main Tariff Index
Effective Date: 10/01/1993, Docket: RS92- 48-001, Status: Effective
Original Sheet No. 67 Original Sheet No. 67 : Effective
GENERAL TERMS AND CONDITIONS
2. QUALITY OF GAS
2.1 Quality Standards: The gas which Riverside receives hereunder
from Shipper for transportation (and the gas which Riverside
delivers hereunder to Shipper) shall be merchantable gas, at all
times complying with the following quality requirements:
(a) Heating Value: The gas shall have a gross heating value of
not less than nine hundred fifty (950) Btus per cubic foot,
wet basis.
(b) Freedom from Objectional Matter: The gas received and
delivered hereunder:
(1) Shall be commercially free from sand, dust, gums,
water, crude oil, impurities and other objectional
substances which may be injurious to pipelines or
which may interfere with its transmission through
pipelines or its commercial utilization.
(2) Shall not contain more than one-quarter (1/4) grain of
hydrogen sulfide or more than ten (10) grains of total
sulphur per one hundred (100) cubic feet.
(3) Shall not contain more than one percent (1%) of volume
of carbon dioxide.
(4) Shall not exceed one hundred twenty degrees (120þ)
Fahrenheit in temperature at the point of receipt.
(5) Shall be as free of oxygen as practicable through the
exercise of all reasonable precautions, and shall not
in any event contain more than one percent (1%) of
oxygen by volume.
(6) Shall not contain in excess of seven (7) pounds of
water vapor per million cubic feet.
(c) Acceptance of Gas not Meeting Quality Standards: Riverside
shall have the right to accept receipt of any gas not
complying with the foregoing quality specifications subject
to its right at any time thereafter to require that the
quality specifications stated above shall be observed for
all future receipts.