7.2 Failure to Conform to Quality Specifications - If
the gas offered for delivery by Norte¤o shall fail
at any time to conform to any of the
specifications set forth in Section 7.1, then
Buyer or Shipper shall notify Norte¤o of such
deficiency and thereupon may at Buyer's or
Shipper's option refuse to accept delivery pending
correction by Norte¤o.
7.3 Unless otherwise provided in the Service Agreement
or applicable Rate Schedule, the provisions set
forth in this Section 7.3 shall apply to all gas
delivered to Norte¤o by Shipper.
(a) all gas shall have a total heating value of
not less than one thousand (1,000) BTUs per
cubic foot, and not more than eleven hundred
BTUs per cubic foot;
(b) all gas shall be commercially free (at
prevailing pressure and temperature in
Norte¤o's pipeline) from, dust, hydrocarbon
liquids, water, any other substance that
might become separated from the gas in
Norte¤o's facilities, and Shipper shall
furnish, install, maintain and operate such
drips, separators, heaters, and other
mechanical devices as may be necessary to
effect compliance with such requirements
(after having secured the prior approval of
Norte¤o as to the design and construction of
such facilities, which approval shall not be
unreasonably withheld);
(c) all gas shall not contain more than five
grains of total sulphur, nor more than one
fourth (1/4) of one grain of hydrogen
sulphide per one hundred (100) cubic feet;
(d) not contain more than two-tenths of one
percent (0.2%) by volume of oxygen, and
Shipper shall make every reasonable effort to
keep the gas free of oxygen;