7. QUALITY
7.1 Specifications. The Gas delivered by either party to the other
hereunder shall be of such quality that it shall meet at least the
following specifications:
(a) Be commercially free from objectionable odors, dirt, dust,
iron particles, gums, gum-forming constituents, gasoline,
PCB's, and other solid and/or liquid matter, including but
not limited to water, gas treating chemicals and well
completion fluids and debris, which may become separated
from the Gas during the transportation or storage thereof.
(b) Contain not more than one half (1/2) of one grain of
hydrogen sulphide per one hundred (100) cubic feet, as
determined by the cadmium sulfate quantitative test, nor
more than ten (10) grains of total sulphur per one hundred
(100) cubic feet.
(c) The Gas delivered hereunder shall not contain more than two-
tenths of one percent (0.2%) by volume of oxygen, shall not
contain more than two percent (2%) by volume of carbon
dioxide, shall not contain more than two and one half
percent (2.5%) by volume of nitrogen, and shall not contain
a combined total of carbon dioxide and nitrogen components
of more than four percent (4%) by volume.
(d) Have a heating value of not less than nine hundred and
sixty-seven (967) Btu's per cubic feet and not more than one
thousand one hundred and ten (1110) Btu's per cubic feet.
(e) Have a temperature of not more than one hundred twenty
degrees Fahrenheit (120 degrees F), nor less than forty
degrees Fahrenheit (40 degrees F).
(f) Have been dehydrated by the tendering party, by any method
other than the use of a calcium chloride as desiccant, for
removal of entrained water in excess of seven (7) pounds of
water per million (1,000,000) cubic feet of Gas as
determined by dew-point apparatus approved by the Bureau of
Mines or such other apparatus as may be mutually agreed
upon.
7.2 Rejection of Gas. Either party shall be entitled to reject any
Gas tendered to it by the other party which does not meet the
minimum specifications of Section 7.1 hereunder. Acceptance of
such Gas does not constitute any waiver of Steckman Ridge's right
to refuse to accept similarly nonconforming Gas.