(c) The measurement equipment of the operator of the
interconnecting facility will be for check purposes only and, except as
expressly provided in these General Terms and Conditions, will not be used in
the custody measurement of gas.
14.11 Calibration and Test of Measurement Equipment. White River will
verify the accuracy of all measurement equipment at reasonable intervals.
White River will provide notice of regular inspections and calibrations of
measurement equipment and any routine orifice plate changes to the operators
of interconnecting facilities, and the operators or other contractually
designated representative of Shippers may attend the inspections or plate
changes. White River shall not be required to verify the accuracy of its
equipment more frequently than once in a 90-day period. In the event an
operator of an interconnecting facility or their contractually designated
representative notifies White River that it desires a special test of any of
White River's measurement equipment, the parties shall cooperate to secure
prompt verification of the accuracy of such equipment. Any operator of an
interconnecting facility or their contractually designated representative
requesting such a special test of White River's measurement equipment shall
bear White River's out-of-pocket costs of the test if the equipment is found
to be accurate within one percent (1%).
14.12 Correction of Measurement Errors. If any measurement equipment is
found to be inaccurate, the equipment will be adjusted immediately to measure
accurately. If the measurement equipment in the aggregate is found to be
inaccurate by one percent (1%) or more at a recording corresponding to the
average hourly rate of gas flow for the period since the last preceding test,
any payments based upon inaccurate measurement will be corrected at the rate
of such inaccuracy for any period that is known definitely or agreed upon. In
the case where the period is not known or agreed upon, such correction will be
for a period extending over one half of the time elapsed since the date of the
last test.