Honeoye Storage Corporation
Original Volume No. 1A
Contents / Previous / Next / Main Tariff Index
Effective Date: 08/01/2000, Docket: CP00- 93-003, Status: Effective
Original Sheet No. 87 Original Sheet No. 87 : Effective
and Transporter, on Customer's behalf, and installed so that it may
properly record the gross heat content of the gas at the Point of
Injection/Withdrawal. Where a calorimeter is used, the arithmetical
average of the hourly gross heat content recording each day shall be
deemed to be the heat content of the gas for that day. Such Calorimeter
shall be checked at least once each month to assure its proper operation
and accuracy. An appropriate certified gas sample of known heat content
shall be used to check the calorimeter accuracy.
6.2 Computations of volume from Meter Readings and Registrations: The volume of
gas delivered or redelivered hereunder shall be determined in the manner specified
in AGA Gas Measurement Committee report No. 3 ("AGA report No. 3")
published in 1978, as such publication may be revised from time to time, or of
other reports and publications which are mutually acceptable to Seller and
Transporter, on Customer's behalf.
6.3 Flowing Temperature: The flowing temperature of gas delivered and redelivered
hereunder shall be determined by means of a standard recording thermometer or
other instrument of standard manufacture accepted in the industry. The flowing
temperature used in determining the flowing temperature factor for each meter
chart shall be the arithmetical average of the temperature shown by the recording
instrument during the period of time when gas is passing through the meter.
6.4 Specific Gravity: The specific gravity of the gas delivered and redelivered
hereunder shall be determined by a recording specific gravity instrument of
standard manufacture or other method mutually acceptable to Seller and
Transporter, on Customer's behalf, and installed so that it may properly record the
specific gravity of the gas at the point of delivery. The arithmetical average of the
hourly specific gravity recording each day shall be deemed to be the specific
gravity of the gas for that day. Such instrument shall be checked by the use of an
Edwards Balance, or by any other method , at intervals mutually agreed to by
Seller and Transporter, on Customer's behalf.
6.5 Supercompressibility: Adjustment for the effect of supercompressibility for gas
delivered and redelivered hereunder shall be made according to the provisions of
AGA Report NX-19 as such publication may be revised from time to time, or of
other reports and publications which are mutually acceptable to Seller and
Transporter, on Customer's behalf, for the average conditions of pressure, flowing