(f) Temperature. The gas shall not have a temperature of more than one
hundred twenty degrees (120º) Fahrenheit or less than forty (40º) Fahrenheit.
(g) Water Vapor. For gas received into Pipeline's system, such gas shall
not contain in excess of seven (7) pounds of water vapor per million cubic
feet.
(h) Liquefiable Hydrocarbons. The gas shall not contain liquid hydrocarbons
or hydrocarbons liquefiable at temperatures warmer than 15ºF and normal
pipeline operating pressures of 100 - 1440
psig.
(i) Microbiological Agents. The gas shall not contain, either in the gas or
in any liquids with the gas, any microbiological organism, active bacteria or
bacterial agent capable of contributing to or causing corrosion and/or
operational and/or other problems. Microbiological organisms, bacteria or
bacterial agents include, but are not limited to, sulfate reducing bacteria
(SRB) and acid producing bacteria (APB). Tests for bacteria or bacterial
agents shall be conducted on samples taken from the meter run or the
appurtenant piping using American Petroleum Institute (API) test method API -
RP38 or any other test method acceptable to Pipeline and Shipper which is
currently available or may become available at any time.