13.5 Specific Gravity
Specific gravity shall be determined by means of a
recording gravity instrument (Gravitometer or
Chromatograph) of standard manufacture acceptable to
both Sabine and Upstream or Downstream Operator and
installed to properly record the specific gravity of
the gas received and delivered hereunder. The
average specific gravity recorded during the twenty-
four (24) hour period from the recording gravity
instrument shall be deemed to be the specific gravity
of the gas for that Day. All composite samples shall
be retained for a minimum period of thirty (30) Days
for verification in the event of a disagreement.
13.6 Heating Value
Heating value shall be determined by a calorimeter,
chromatograph, or other Btu measurement device of
standard manufacture acceptable to both Sabine and
Upstream or Downstream Operator and installed to
properly record the heating value of the gas received
and delivered hereunder. The average heating value
recorded during the twenty-four (24) hour period from
the Btu recording device shall be deemed to be the
heating value of the gas in British thermal units for
that Day. The Btu recording device shall be tested
using a laboratory grade sample of known Btu and
component content. All composite samples shall be
retained for a minimum period of thirty (30) Days for
verification in the event of a disagreement.