North Baja Pipeline, LLC
Original Volume No. 1
Contents / Previous / Next / Main Tariff Index
Effective Date: 02/15/2008, Docket: CP06- 61-004, Status: Effective
First Revised Sheet No. 106 First Revised Sheet No. 106 : Effective
Superseding: Original Sheet No. 106
GENERAL TERMS AND CONDITIONS OF SERVICE
(Continued)
2. QUALITY OF GAS
2.1 Quality Standards: The gas which Shipper delivers hereunder to
NBP for transport (and the gas which NBP transports hereunder for
Shipper) shall be merchantable gas at all times complying with the
following quality requirements:
(a) Heating Value: The gas shall have a Gross Heating Value of
not less than nine hundred ninety (990) and not greater than
one thousand one hundred fifty (1150) Btus per standard
cubic foot on a dry basis, but with the consent of Shipper,
NBP may deliver gas at a lower Gross Heating Value.
(b) Gas Quality (at the pressure and temperature at which the
gas is delivered): The gas:
(i) Shall be commercially free from sand, dust, gums,
crude oil, impurities and other objectionable
substances.
(ii) Shall not have a hydrocarbon dew-point in excess of
twenty degrees (20 o) Fahrenheit at pressures up to
six hundred (600) psig.
(iii) Shall not contain more than one-quarter (1/4) grain of
hydrogen sulfide per one hundred (100) standard cubic
feet.
(iv) Shall not contain more than three-quarters (0.75)
grain of total sulphur per one hundred (100) standard
cubic feet.
(v) Shall not contain more than two percent (2%) by volume
of carbon dioxide.
(vi) Shall not contain more than three percent (3%) total
diluents (the total combined carbon dioxide, nitrogen,
helium, oxygen, and any other diluent compound) by
volume.
(vii) Shall not contain more than seven (7) pounds of water
vapor per one million (1,000,000) standard cubic feet.
(Continued)