GENERAL TERMS AND CONDITIONS
(Continued)
5. MEASUREMENT & MEASUREMENT EQUIPMENT (Continued)
(c) If no tests have been performed to determine the
degree of inaccuracy, or measurement equipment
is out of service, the quantity of Natural Gas
shall be estimated as follows:
(1) by using the registration of any existing
and agreed upon check equipment considered
by Transporter or Connecting Party to be
registering accurately, or in the absence
of such equipment,
(2) by correcting the error, if the quantity
of percentage of error is ascertainable by
calibration, test, or mathematical
calculation, or if neither of the two
foregoing procedures are applicable,
(3) by relating the quantity of receipt or
delivery to receipts or deliveries during
periods under similar conditions when the
measurement equipment was deemed to have
been registering accurately.
5.8 Electronic Natural Gas Measurement ("EGM") Technical
Requirements
(a) Accuracy. Where EGM is used, the system shall
use instruments designed to provide overall
measurement accuracy of ñ1.0% of flow, taking
into account all the sources of error, including
calibrated span of instruments, linearity,
hysteresis, repeatability, ambient temperature,
stability, vibration, and power supply
fluctuation.