Central New York Oil And Gas Company, LLC

Original Volume No. 1

 Contents / Previous / Next / Main Tariff Index

 

 

Effective Date: 12/01/2001, Docket: CP00- 61-001, Status: Effective

Original Sheet No. 92 Original Sheet No. 92 : Effective

 

GENERAL TERMS AND CONDITIONS (continued)

 

(c) other method mutually agreed upon by both

parties.

 

For the purpose of calculating injections and

withdrawals, the heat content of the Gas so

determined at each such point shall be deemed to

remain constant at such point until the next

determination. The unit of quantity for the

purpose of determining total heating value shall

be one (1) cubic foot of anhydrous Gas at a

temperature of sixty degrees (60) Fahrenheit and

an absolute pressure of 14.73 psia, dry.

 

7.2 Freedom from Objectionable Matter. The Gas

injected and withdrawn hereunder:

 

(a) shall be commercially free, at

prevailing pressure and temperature in

Seller's equipment and facilities, from

objectionable odors, dust or other solid or

liquid matter which might interfere with its

merchantability or cause injury to or

interference with proper operation of the

lines, regulators, meters and other equipment

and facilities of Seller.

 

(b) shall not contain more than one

quarter (.25) grain of hydrogen sulfide per

one hundred (100) cubic feet of Gas, as

determined by methods prescribed in Standards

of Gas Service, Circular of the National

Bureau of Standards, No. 405, page 134 (1934

edition), and shall be considered free from

hydrogen sulfide (H2S) if a strip of white

filter paper, moistened with a solution

containing five percent (5%) by weight of

lead acetate, is not distinctly darker than a

second paper freshly moistened with the same

solution, after the first paper has been

exposed to the Gas for one and one-half (1-

1/2) minutes in an apparatus of approved

form, through which the Gas is flowing at the

rate of approximately five (5) cubic feet per

hour, the Gas from the jet not impinging

directly upon the test paper; or the H2S

content may be determined by an instrument of

approved type and by approved methods

agreeable to the parties;

 

(c) shall not contain more than twenty

(20) grains of total sulfur (including the

sulfur in any hydrogen sulfide and

mercaptans) per one hundred (100) cubic feet

of Gas;

 

(d) shall not at any time have an oxygen content

in excess of two-tenths of one percent (0.20%) by volume and

the parties hereto shall make every reasonable effort to

keep the Gas free of oxygen;